PascalVision 20/100 |
|
 |
-
For
monitoring, control and display of FFU differential pressure and laminar flow velocity
-
4-20 mA Analog Output (scalable and configurable)
|
| |
RS 232 Digital output
(ASCII string or complex protocol)
Display Window Equipped
Measurement Ranges: -20~20 Pa (20)
-100~100 Pa (100)
Resolution: 0.016 Pa (20)
0.07Pa (100)
Accuracy
(20):
<4Pa: ±0.05Pa
≥4Pa: ±1.5% of measured value
Accuracy
(100):
<17Pa: ±0.25Pa
≥17Pa: ±1.5% of measured value
Hysteresis: none
Drift: < 0.1 Pa per year |
|
Download
PascalVision Catalog |
Download Manual/Control Software |
|
|
PascalDat 20/100 |
|
 |
|
| |
RS 232 Digital output
(ASCII string or complex protocol)
Measurement Ranges: -20~20 Pa (20)
-100~100 Pa (100)
Resolution: 0.016 Pa (20)
0.07Pa (100)
Accuracy
(20):
<4Pa: ±0.05Pa
≥4Pa: ±1.5% of measured value
Accuracy
(100):
<17Pa: ±0.25Pa
≥17Pa: ±1.5% of measured value
Hysteresis: none
Drift: < 0.1 Pa per year |
|
Download PascalDat Catalog |
Download Manual/Control Software |
|
|
PascalSwitch 20/100 |
|
 |
-
For
monitoring and alarm purposes, and stand alone applications
-
Dual relay Output
(Break and make contact)
|
| |
Measurement Ranges: 0~20 Pa
(20)
0~100 Pa (100)
Resolution: 0.016 Pa (20)
0.07Pa (100)
Accuracy
(20):
<4Pa: ±0.05Pa
≥4Pa: ±1.5% of measured value
Accuracy
(100):
<17Pa: ±0.25Pa
≥17Pa: ±1.5% of measured value
Hysteresis: none
Drift: < 0.1 Pa per year |
|
Download
PascalSwitch Catalog |
Download Manual/Control Software |
|
|
Calibox 100 DP Instrument Mobile
Calibrator |
|
 |
|
| |
Generation Range: 0~100 Pa
Resolution: 0.07 Pa
Accuracy: 0.25% Full Scale
Hysteresis: none |
|
Download Calibox Catalog |
|
|
|
HygroDat 100 Humidity Transducer |
|
 |
|
| |
Measurement Ranges:
Humidity: 6~100% RH / Accuracy: 0.5%
Temperature: -20~80°C / Accuracy: 0.2K
Dew point: -40~60°C
Enthalpy: 0~166 kJ/kg
Mix Ratio: 0~49 g/kg |
|
|
|
|
|
Hygromate Handheld Humidity and
Temperature Probe |
|
 |
|
| |
Measurement Ranges:
Humidity: 0~95% RH / Accuracy: 2%
Dewpoint: -50~50°C
Mix Ratio: 0~83 g/kg |